Monday, December 31, 2018

Multi-Point Level Control from Robertshaw

Flow Factor provides Level Control for Industry
Schneider Electric/Robertshaw Capacitance Level Control

For a quote,
please fill out our Robertshaw Parts Form HERE!

Robertshaw 5400 Level-Lance Multi-Point On/Off Level Controller


GENERAL DESCRIPTION
The ROBERTSHAW Level-Lance Model 5400A is a microprocessor based, multi-point On-Off capacitance type level detection system. Utilizing the Pulse Frequency Modulation (PFM) method of signal transmission ensures that accuracy, repeatability and longevity are enhanced over level systems using conventional analog transmission schemes. The PFM transmitter, normally mounted directly on the sensing probe, requires no calibration or adjustments of any kind. The control unit can be mounted up to one mile from the PFM transmitter without requiring any special type of interconnecting wire or cable. Two wires are all that is required. The PFM transmitter does not require any primary power because it receives its operating power from the control unit over the same two wires used to transmit the level signal.

The PFM (Pulse Frequency Modulation) transmitter is also designed to provide electrostatic protection at the probe input. It transmits a frequency modulated pulse signal to the microprocessor based control unit. The variation in the frequency of the pulse is proportional to the product level on the sensing probe. The microprocessor in the control unit receives the pulse and processes it to extract the level information. The microprocessor then compares this level information to the “AUTO-SET” calibration data stored in the non-volatile memory. When the level data coincides with this previously stored data, the appropriate output relay is either activated or deactivated, to give the desired control action. The total system design has been optimized to yield the highest possible levels of both EMI and RFI rejection.

The Model 5400A Level-Lance is calibrated by means of the “AUTO-SET” feature. This feature permits all calibration of the unit to be done by the simple act of pushing a button.

The Model 5400A Level-Lance is designed with plug-in type relay output modules to allow for easy configuration changes. Relay outputs can be added or removed in the field by the user. The control unit has the capability of having up to four relay output modules installed. The PFM input is optically coupled for better noise immunity. 


Each relay output can be individually configured for:
  1. A)  Fixed minimum or adjustable differential (deadband).
  2. B)  High or Low level fail safe.
  3. C)  Adjustable time delay.
These selections are made by means of miniature selector switches located on the individual relay output modules. All relay output module functions are totally independent of other relay output modules.
An additional switch located on the main (microprocessor) board allows for selection of the overall operating mode as follows:
  1. A)  Normal operation.
  2. B)  Load sharing. This mode permits the sequential
    operation of two to four pumps or motors,
    alternated or rotated to prolong their life.
  3. C)  Test (self diagnostics). LED’s indicate transmitter (PFM) or receiver (RCVR) failure or
    calibration (CAL) error. 

Robertshaw Level Lance Multi-Point Controller (Probe is Extra)

FEATURES AND BENEFITS

  •   Microprocessor Based
  •   “Auto-Set” (Pushbutton Calibration
  •   Modular Construction
  •   Multi-Point Control (1-4) Relays, Using Only One Sensor (Probe)
  •   Economical, Cost Much Less Than 4 Individual Controls
  •   Up To 1 Mile Signal Transmission PFM to Controller Using 2 Plain Wires
  •   Independent Time Delay and Adjustable Differential For EACH Relay
  •   Lead/Lag Feature For Automatic Pump Alternation
  •   Heavy Duty 10 Amp Relays
  •   Self-Diagnostics With LED Failure Indication
  •   Designed For Maximum EMI and RFI Rejection
  •   Optical Isolation Between PFM and Controller
  •   Non-Volatile Calibration Memory
  •   Optional Indicating Lights

      Optional AC or DC Supply Power Optional
      Enclosures (NEMA 4, 4X or Explosion-Proof 

      UL and c-UL Listed 



SPECIFICATIONS

ELECTRICAL/ELECTRONIC:
Supply Voltage
Standard - 120/240 VAC
10%, 50/60 Hz Optional - 18 to 30 VDC
Supply Power
Exp-
proof w/lights ... 48 Watts Max All other models ...... 20 Watts max
Control Range ................. 0 to 3000 pF
Adjustable Differential ....... 0.2 pF to 100% of Control Range
Fixed Differential .............. 0.1 pF
Adjustable Time Delay ...... 0 to 99 seconds
Ambient Temperature Effect
0.005 pF/deg F or 0.01%/deg F, whichever is greater
Supply Variation Effect ...... None Linearity ......................... 0.5% Resolution ...................... 0.1 pF Repeatability ................... 0.1 pF
Relay Output
Electro-Mechanical, DPDT

10 A @ 30 VDC,120 VAC, 240 VAC RES; 5 A @ 120 VAC IND;
3 A @ 240 VAC IND;
1/3 HP @ 120 VAC, 240 VAC

Maximum Distance Between Probe
and Transmitter ............... Fifteen (15) feet
Type of Interconnecting Cable
Coaxial, RG-62/U, rated 80
C minimum
Maximum Distance Between Transmitter and Controller ....................... One (1) mile
Type of Interconnecting Cable
Two (2) wires, twisted pair in grounded metal conduit or twisted, shielded pair in non-metallic conduit.
14 AWG Maximum rated 80
C minimum 

ENVIRONMENTAL:

Ambient Temperature ....... -30to +140F (-34to +60C)
Storage Temperature ........ -40to +158F (-40to +70C)
Relative Humidity ... 0 to 95% (non-condensing) Vibration ........................ 2 G, 10 to 200 Hz Shock .................. 75 G for 11 msec

ENCLOSURE:

Controller Raintight -
Standard -
Optional -
Optional - Explosion Proof -
PFM Transmitter Raintight -
Standard -
Optional -
Polyurethane painted steel, Type 4 Fiberglass, Type 4X Stainless steel, Type 4X
Cast aluminum,
UL Listed
Class I, Group D;
Class II, Group E, F & G; Class I, Zone 1, Group IIA c-UL Listed

Class I, Group C & D; Class II, Group E, F & G; Class I, Zone 1,Group IIB
Polyurethane painted cast aluminum, Type 4
Gray epoxy painted cast aluminum, Type 4X 

For a quote,
please fill out our Robertshaw Parts Form HERE!

Flow Factor
216-765-4231
www.flowfactor.com

Robertshaw 5400 Multi-Point Capacitance Level Control

No comments:

Post a Comment