Capacitance instrumentation is an example of measurement where the
process variable (level for example) causes a capacitance signal to be
generated that the instrument acts upon to provide an output or signal
proportional to the change in the process variable.

Electrical "capacitance" is the property (or measure) of two conductors (or plates), electrically insulated from each other, to store energy when a
difference of electrical potential exists between them. Under these
conditions, an electrostatic field exists between the conductors and the
amount of stored energy is a function of the area, spacing, electrical
potential and the material between the conductors.

The unit of measure of capacitance is the "Farad", however the "pico-farad" is used in capacitance instrumentation. This is abbreviated "P? and is equal to 1 x 10 to the -12 Farads. Most capacitance instrument manufacturers specify the operating range, sensitivity, adjustments, etc. of the instrument in pico-farads.

The amount of "capacitance" in any given capacitor is determined by the area, spacing of the plates and the material between the plates.  This can be
seen in the equation for the capacitance of a simple parallel plate capacitor as shown

Capacitance = 0.225 K x A/D
Where :  K = Dielectric constant of material between the plates
               A = Area of the plates
               D = Distance between the plates

The equation indicates that the capacitance is directly proportional to the dielectric constant, directly proportional to the area of the plates, and inversely proportional to the spacing or distance between the plates.
Dielectric constant (K) is a dimensional number to relate the amount of capacitance generated when anything other than air is used as the material between the plates. For example, if some material was inserted in the "air" capacitor that caused the capacitance to double, the material would have a dielectric constant of 2 or twice that of air. The dielectric constant number, then relates capacitance generated to that of air.
All materials have a dielectric constant value. For practical purposes, all gases (including air) have a dielectric constant equal to (1). If then, the air in an air-filled capacitor was displaced by a liquid, the capacitance increase of the capacitor would be directly proportional to the change in dielectric constant (K) between the liquid and air.
This is the fundamental concept upon which all capacitance instrumentation is based.
Generation of the Capacitance Signal
For most applications of capacitance instruments, the method used to
generate a capacitance signal consists of placing a rod type electrode
(probe) in contact with, or in close proximity, to the process material.
If, for example, it were a level application, the changing level of the
material within the vessel would create a change in the measured
capacitance at the probe. The magnitude of the capacitance change is
determined by the geometry of the installation, probe type, vessel and the product being measured.

When measuring a non-con0uctive material, the change in level is
indicated by a change in the dielectric constant (K) of the material between the plates of the capacitor. As the level rises, the air or gas normally surrounding the probe is displaced by material having a higher dielectric constant. The grounded metal vessel acts as the ground plate, and the mass of material between the plates is the variable. As the level changes, the capacitance varies because the dielectric between the electrodes has changed.

When measuring a conductive rather than the vessel wall acts as the ground plate. In this case, the area (A) in material, the measured material itself, contact increases as the level increases, resulting in a change in the capacitance of the system. Insulated probes are used in this type of application to separate the conductive material from the probe. The thickness of the insulation is the distance (D) between the plates.

In proximity (non-contacting) type sensors, the distance (D) between the plates decreases as the level rises. If the material is conductive, the surface of the material forms one plate of the capacitor. If the material is nonconductive, two capacitors are in series - one through the air, and one through the measured material. For either conductive or non-conductive material, the capacitance changes as the material approaches the probe, because the distance or dielectric between the electrodes has changed.

Successful application of any capacitance instrument depends upon an
adequate change being generated by the process. The word "change' is
emphasized since all capacitance measurement systems start with an
initial or "terminal" capacitance value and increase to some final value as a function of the process variable. The change in the capacitance is denoted delta C. Each instrument has a specified minimum capacitance change upon which it will operate, therefore, an estimation of the generated capacitance signal must be made to ensure satisfactory instrument performance.



TYPES OF CAPACITANCE MEASUREMENT

1. Continuous
a. Overall with indication and/or output
b. Interface with indication and /or output
c. Proxlmity with indication and/or output
d. a, b, or c with relay/alarm outputs

Note: Continuous interface (immiscible liquids only) measurement can only be accomplished when one product is conductive and the other is nonconductive (oil/water, toluene/water, etc.) A vertical mounted probe is used and, in most cases there can only be two variables involved and tank should always be full with no air. Exceptions are where the third variable is very close in dielectric constant to the non-conductive product or where you can use a sheath to eliminate the error introduced by the third variable. The sheath will extend through the upper third variable (air for instance) and below the lowest point the overall liquid levels will ever reach. In all interface measurements you will be measuring the conductive product. Interface applications should be considered by individual application. Emulsion layers are also a problem.

2. On/Off Point Level (s) with or without Differential

a. Single or multiple point
b. Interface (no differential)
c. Proximity

Note: On/Off interface measurement uses a horizontal mounted probe and the product being measured must differ in dielectric/conductivity than the other products in the tank. Emulsion layers are a problem.

Principle of Short Stop Operation

In point level control, a conductive coating on a horizontally mounted
probe often causes false relay trips when the material level has risen
above, and then falls below, the detection point. The current passes
through this coating to the vessel wall, completing the circuit. The point level switch continues to indicate - now incorrectly - that the level is above the alarm point.
The Short-Stop feature ignores the effect of conductive material buildup. A second element added to the probe is electronically maintained (or driven) at the same voltage and frequency as the measuring tip. This means that no current can flow through the coating to the vessel wall. When the actual level reaches the bare tip, current can flow to the tank wall only through the material being detected. In this way, the driven shield technology eliminates erroneous signals due to current passing through the material coating the probe.

{Picture}

Probe Installation

Horizontally mounted rod type probes must be installed in the vessel at the desired point of level detection. This type of installation provides the closest control (smallest deadband) in that a small change at or near the probe will produce a large capacitance change. On applications involving viscous liquids or materials that have a tendency to "cling" or "build-up" it is recommended that the probe be mounted on a slight downward angle to permit draining of the material from the probe. The instrument actuation point should be set so that the high level point is always below the gland" If the horizontally mounted probe is to be installed in a recess or nozzle, the use of a "sheathed" probe is recommended. This type of probe has an inactive (sheathed) portion near the mounting gland so as to eliminate false operation if material collects or packs within the recess or nozzle.

{Picture}


Vertically mounted probes can be mounted in either the top or bottom of the vessel with the probe midpoint corresponding to the approximate desired level detection point for On-Off instruments. This allows a variation in the level detection point up and down the length of the probe by means of the instrument zero adjustment.
Proportional instruments for level measurement require a probe longer
than the intended measurement span. For probe lengths exceeding 10 feet, a flexible probe is recommended, primarily for shipping considerations. Long flexible cable probes are offered with optional lower end fittings for weights or tie-downs. If top mounted probes are mounted through a nozzle and process has high vapor content or subject to condensate forming in the nozzle, then a sheath should be considered.

Continuous Level Measurement in Liquid Products

The Continuous measurement of level in a tank containing liquid can be
made by a number of methods. One of the simpler and more reliable
methods is by capacitance techniques. The liquids and slurries which can
be measured by capacitance covers a wide range of products, including
aqueous solutions, hydrocarbons, acids, alkalies and slurries of rock
products, paper products, etc. The "self-cleaning" characteristic of Teflon
covered probes, as well as their excellent chemical resistance, make the
capacitance method almost universal in its application to liquid level
measurement. An advantage of capacitance techniques in liquid level
measurement is that the specific gravity of a product is not a factor except in terms of viscosity (ability of the product to freely flow or drain from the probe.

Typical Applications

The probe can be either the rigid or flexible type. The rigid types are
usually limited to 10 feet in length, while flexible types can be made up to 100 feet or more. Figure 1 shows graphically the range of dielectric constants with various products. The low dielectric materials are liquefied gages such as LOX and nitrogen - typically these products range from 1.05 for helium to 1.5 for oxygen. Hydrocarbons will range from 2.0 to 6.0 with the heavier oils being the higher of the group. Next is the family of alcohols and ketones which range from 12 to 35. The very high dielectrics are aqueous solutions and many of the common acids or alkalies. These are in the range of 75 to 90.

Probe Selection and Location

Very low dielectric materials will produce low capacitance changes when compared between air (vessel empty) and the vessel full capacitance. The
liquefied gases have such low dielectric constants that the total capacitance
change with standard probes is insufficient to produce full span outputs.
Therefore, the probe or installation must be modified to produce a larger
capacitance change. In low dielectric liquids, that are free of solids, this is
most easily accomplished by using a concentric probe. This probe will
produce several times more change per foot of measured product on low
dielectric materials than the standard probes.
The minimum range (span) of the Level-Tel instruments is 10 Pf for full
output. It is therefore required that the measured material produce a
capacitance change of at least 10 Pl but a much higher change is
preferred. The maximum range (span) of the Level-Tel varies with the
particular instrument, but ranges from 1OO0 Pf to 6000 Pf and represents
many feet of material when the dielectric is low.
The higher dielectric materials, such as alcohols, aqueous solutions and
acids and alkalies, produce large capacitance changes with only a few feet
of measured material. Therefore, these products are measured most
satisfactorily with standard probes, either rigid or flexible. The probes are
mounted so that they are located in a vertical position within the vessel as
indicated in figure 2. The probe should be located so that the product does
not flow on the probe during filling. In applications where considerable
turbulence of the liquid occurs, it is suggested that a 'stilling well" be
installed.
Continuous Level Measurement in Granular Products

General
Continuous level measurement of granular products is one of the more
difficult measurements because of the physical characterisitics of the
materials. Capacitance techniques offer one of the more accurate, reliable
and simplest methods of continuous level measurement of granular or
powdered materials in silos, hoppers and bins.

Typical Applications

A probe, either rigid or flexible, is installed within the vessel in such a
manner that the measured material will surround the probe. The
capacitance, as sensed by the probe, will vary directly with the level
(height) of the material in the vessel. Figure 3 shows a typical graph of
dielectric constant versus capacitance generated for some common low
dielectric products. Remember that the net change is the difference
between air and the product being measured. For example, wheat flour has
a dielectric constant of approximately 3.0. With a flexible probe mounted
concentrically in a 24" vessel, wheat flour will generate approximately 9 Pf
per foot on the probe. With air surrounding the probe (vessel empty), the
capacitance is approximately 3 .5 Pf/ft Therefore, the wheat flour will
produce a net capacitance change of 5.5Pf/ft Avessel of 15 feet in height,
having a "full" design point of 12 feet, would produce a new capacitance
change of 56 Pf ( 12' x 5.5 Pf/ft.)

The Level-Tel transmitters have a measuring range (span) from 10 Pf
minimum to several thousand Pf maximum. The minimum full span of
level for wheat flour is approximately 1,8 feet (10 Pf divided by 5.5 Pf/ft),
while the maximum span could be well over 100 feet. Notice that the span
can vary from a few feet to many feet dependent upon the material being
measured.

A general rule of thumb is that low density products, those which weight
only a few pounds per cubic foot, generally have low dielectric constants
while high density materials (in the same family) will have higher
dielectric constants. The change in dielectric constant with density for a
given family of products results from the particle size and shape, which
affects the amount of air entrapment in the material. The greater the air
entrapment, the lower the dielectric constant. Mineral oxides generally
have higher dielectric constants than flours, cereals, etc. because they have
higher densities.

Probe Selection and Location
The probe must be mounted to hang vertically in the vessel so that it may
continuously sense the rise or fall of the material. The probe, if the rigid
type, is entered and supported at the top by its gland assembly. Typically,
rigid probes are limited to 10 feet in length. For vessels requiring longer
probes, the flexible type is used and is either mounted by means of its
gland or suspended by means of insulators, which are supported by
mechanical means within the vessel. Typically the probe is mounted
midway between the center and sidewall of the vessel, as shown in figure
4. ln this way, it measures the average volume of material in the vessel
even when the product has a large angle of repose. Flexible probes are not
fastened or tethered to the bottom of the vessel in most granular
applications.

{picture}

Proximity (Non-Contact) Measurements

General
On many level control applications, it is impractical to use immersed
probes as the sensing element. Products which have adhesive
characteristics can often be controlled within close limits through the use
of a non-contacting probe which is placed above the product surface. Many
products, having a tendency to congeal and harden when exposed to air or
changes in temperature, can make use of this technique. Other applications
include those where thickness of product must be maintained within tight
specified limits. All of these applications can make use of "proximity."

Typical Application Data

There are 2 major areas which must be considered when using proximity :
1. The size of the probe (or flat Plate)
2. The dielectric of the material being sensed

The first consideration is the size of the probe which can be installed in the
vessel whose level is to be controlled. The area of the probe must
correspond to the material level control requirements. Reference figure 5
shows the relationship between the area of the sensing probe and the
capacitance change which will result as a conductive material changes its
level. Consider a typical application where it is desired to control the level
of a conductive adhesive material : the material is in a heated vat and is
used as a coating product for paper, fabrics, etc. It is desired to control the
level to + or - 0.25" and the maximum free space available in the vat will
permit a probe approximately 6 x 16 inches. This probe should be spaced
from the sides of the vat and any rolls or mechanisms by at least one inch.
The active area of the plate will be 6 x 16 : 96 square inches. Referring to
figure 5, it will be observed that for a plate of 100 sq. in., the level will
move from a minimum distance of 1 inch to a maximum of 2.5 inches to
produce a capacitance change of 13.5 Pf, (9 Pf to 22.5 Pf = 13.5 ).

The second curve, which shows the capacitance generated for a 25A sq, in.
plate, would produce a change in capacitance of 17 Pf for a level change of
approximately two inches. To produce a change of 10 Pf would require a
total level change of approximatety 3 / 1 inch. Notice that the portion of the
curve considered has been through the center of the curve. This should
always be done for any particular plate area since it is in this area that the
capacitance change is most nearly linear to level change. Other curves are
easily calculated from the formula and it is suggested that for any
particular application, the curve be plotted for the probe area in order to
determine the desired spacing capacitance generated.

The second consideration mentioned earlier involved the dielectric
constant of the material. When the material is a conductive fluid or
product, such as aqueous solutions, acids, alkalies, etc. , the curves may be
used directly. When the materials involved have low dielectric constants, a
factor must be applied. For example, if the material is a hydrocarbon
having a dielectric of 3.0 to 4.0, the capacitance change will be
approximately L/6 of the change which would have occurred from a
conductive or high dielectric material. Thus, it will require a much larger
change in level to produce a given capacitance change, BUT THE MAXIMUM
DISTANCE (LOWEST LEVEL POINT) IS LIMITED. DO NOT ATTEMPT TO
REPEATABLY CONTROL A PRODUCT BEYOND APPROXIMATELY 6 INCHES
FROM THE PLATE AT ITS LOWEST POINT.


866-360-9830

Friday, May 30, 2014

Capacitance Level Control Definitions


ROBERTSHAW CAPACITANCE LEVEL

For a quote or part number ID, please click HERE.

Capacitance Level Definitions

High Level Fail Safe (HLFS):
Relay de-Energizes on High Alarm condition. Thus the alarm condition with power failure.  Example: To Keep tank from overfilling with power failure.

Low Level Fail Safe (LLFS):
Relay de_Energizes on Low Alarm Condition. Thus alarm condition with power failure. Example: To Keep pump from running dry and burning up with a ower failure.

Time Delay:
Used for Splashing or wavy processes to prevent cycling on and off.

Response Time:
How fast the unit goes to alarm condition after set point is reached.

C, NO, NC Contacts:
Contacts are normally shown in the non-energized alarm condition – no power, shelf condition.  Relay energizes in non-alarm condition.

POINT LEVEL

ZERO:
This is the SET POINT. Where the desired actuation is to occur.

DIFFERENTIAL:
This is the distance, in Pico-Farads, inches or feet from ZERO to where the RESET is to occur. Sometimes called Deadband or Pump On – Pump Off.

CONTINUOUS LEVEL

ZERO:
The 0% Level point on the sensing probe.

100%:
The full level point on the sensing probe.

SPAN:
The distance in Pico-Farads, from the Zero Level point to the FULL Level Point (100%).

TERMINAL CAPACITANCE:
The Minimum amount of Capacitance present when no product is present in the vessel.
This is:
The Capacitance of the Probe Gland (and sheath and colling extension, if used) PLUS
The Capacitance generated between the probe and the vessel with air as the dielectric. In other words, the absolute minimum value of capacitance generated in that particular probe/vessel installation.

TERMINAL / SPAN RATIO:
The Terminal Capacitance divided by the span capacitance. This ratio must not be exceeded where specified on product specification sheets (all instruments do not have this restriction).

Terminal Adjustment/Zero Adjustment Range/Maximum Zero Suppression:
This is the maximum “Zero Suppression” of the capacitance value at the zero point level in the vessel.  This value cannot be exceeded.

Capacitance Change:
The amount of capacitance difference between ZERO and 100% points in the continuous level measuring instruments; the amount of capacitance difference between product and no product in point level measuring instruments without differential; or the amount of capacitance difference between ZERO and Differential points in Point Level measuring instruments with differential adjustment.

TOTAL CAPACITANCE:
This is the total capacitance value (not capacitance change) with tank of vessel at the 100% level (includes terminal capacitance). This value must not exceed the maximum span of the instrument.

866-360-9830

Wednesday, April 30, 2014

Parker GP Valve Repair Kits

Flow Factor sells Parker Sporlan Aftermarket GP Valve repair kits

The Parker Sporlan Valve division of Parker manufactures refrigeration valves and Steam and Hot water valves (GP Valves) for hotels, restaurants, Hospitals, Prisons and other commercial institutions.

The kits below are for these Parker GP series valves:

GP200  GP207  GP257    1/4 inch valves
GP300  GP307  GP357    3/8 inch valves
GP400  GP407  GP457    1/2 inch valves
GP600  GP607  GP657    3/4 inch valves
GP10A GP1007 GP1057   1  inch valves

Repair kits consist of plunger, diaphragm and seal. (no coils)




Parker Repair Kit for GP 200 valve.
Kit part number is 76723.

Kit part number is 76724.

Parker Repair Kit for GP 257 valve.
Kit part number is 76725.

Parker Repair Kit for GP 300 valve.
Kit part number is 76727.

Parker Repair Kit for GP 307 valve.
Kit part number is 76728.

Parker Repair Kit for GP 357 valve.
Kit part number is 76729.

Parker Repair Kit for GP 400 valve.
Kit part number is 76727.

Parker Repair Kit for GP 407 valve.
Kit part number is 76728.

Parker Repair Kit for GP 457 valve.
Kit part number is 76729.


Parker Repair Kit for GP 600 valve.
Kit part number is 76731.


Parker Repair Kit for GP 607 valve.
Kit part number is 76732.


Parker Repair Kit for GP 657 valve.
Kit part number is 76733.


Parker Repair Kit for GP 10A valve.
Kit part number is 76762.

Parker Repair Kit for GP 1007 valve.
Kit part number is 76799.

Parker Repair Kit for GP 1057 valve.
Kit part number is 76738.

Parker Sporlan Premier After-Market Valves.  The choice for commercial applications.

866-360-9830
info@flowfactor.com

Valve design Form

Sunday, March 30, 2014

Penberthy GH/GL Eductors for Gases

Penberthy/Pentair GL/GH Eductors (jet pumps) for pumping/heating with gas from Flow Factor

Pumping gases using a liquid or gas (steam or air) motive is an effective means of exhausting, evacuating and priming and can be used in a wide variety of operations and industries. These Pentair Penberthy Jet Pumps offer many advantages over other methods of moving gases; they have no moving parts and provide a very simple cost effective method of handling a wide variety of gases and processes. These units are used for all aspects of water treatment, refrigeration, petroleum, petro chemical, brewing, distilling and general process industries.



Features & Benefits:
  • Simple two-piece construction
  • No moving parts to wear out
  • No lubrication
  • Wide variety of special material to suit the most diverse applications
  • Virtually maintenance free
  • Cost effective and inexpensive
  • No power or special installation requirements  



Sizes: 1/2” to 12”
Threaded (Standard) or flanged connections

Operating Pressure Range 20 to 200 psig

Application Range, inches HG. ABS. 0.5 to 30

Materials:
Bronze, Ductile Iron, Carbon Steel, Stainless Steel, PVC, PP, PVDF
Wide variety of special materials also available  

Penberthy jet pumps can also use steam or a gas (air) as the operating media for exhausting, evacuating or priming operations. Primary uses of these types of pumps are for exhausting or evacuating gases. Exhausting means removing gases from an area at a continuous rate while maintaining pressure at a constant level. Evacuation means drawing gases from a defined volume by pumping the vessel down from an initial pressure to a final lower pressure. These steam/gas motive jet pumps meet the industry's most stringent requirements, while providing a simple, low-cost method of transporting gases, operating flawlessly even in the harshest work environments.
Penberthy Models GL and GH operate at pressures from 20 to 120 psig (140 to 830 kPag), the overall capacity being slightly higher when using air as the operating media. U and L Models are single-stage ejectors while the 2NC is a two-stage, non-condensing ejector using steam as the operating media. All these units provide maintenance-free pumping capabilities.
Some uses for steam/gas motive jet pumps include: creating vacuums, exhausting vapors from process systems, evacuating tanks & vessels, priming, fume removal, fluid concentration, humidifying and drying. Industries that could benefit from the use of the jet pumps might include: chemical processing, textile manufacturing, food processing, petroleum production & refining, sterilization and HVAC.

Typical applications involve either exhausting or evacuating. Similar information is needed in order to determine the specific jet pump for your application. Using the information required (listed below), fill out an application form and submit to Penberthy sales representative or the factory to determine the correct pump for your needs.
If Exhausting (Continuous Suction Flow)

Motive:
  • Gas/Steam
  • Pressure (Available)
  • Flow Rate (Available volume-scfm)
  • Temperature
  • Molecular Weight (Gas only)
Suction:
  • Pressure (Inches Hg Abs-kg/sq cm Abs)
  • Flow Rate-scfm
  • Temperature
  • Molecular Weight
Discharge:
  • Pressure (That unit must overcome)

If Evacuating (Sealed Vessel-Pump Down)
  • Volume of Space to Evacuate
  • Required Evacuation Time (Minutes)
MOTIVE:
This function is the power phase of the pumping operation. At this stage, the velocity of the motive media increases as it passes through a nozzle. This phase of the pumping operation takes advantage of the kinetic properties of the motive media, whether it is liquid, steam or gas. Because of this, design differences may exist within the motive connection of the jet pump. For instance, jet pumps with liquid motives use a converging nozzle, since liquids usually cannot be compressed. On the other hand, jet pumps with gas or steam motives use converging/diverging nozzles to achieve trans-sonic flow velocity. The critical flow paths of all Penberthy jet pumps are smoothly machined with no abrupt turns or steps in order to produce the most efficient flow during the motive function. Without this direct flow design and smooth interior surface, the jet pump would not operate at peak efficiency.
SUCTION:
This connection of the jet pump is where the pumping action takes place. The high velocity stream of the motive causes a drop in pressure in the suction chamber. This allows pressure in the suction vessel to push a liquid, steam or gas into the suction chamber of the jet pump. This, in turn, is entrained by the high-velocity motive stream emerging from the inlet nozzle
DISCHARGE:
As the motive flow combines with the suction medium, some kinetic energy of the MOTIVE is transferred to the SUCTION, mixing and discharging at a reduced pressure. The amount of pressure that can be recovered depends on the ratio of the MOTIVE flow to SUCTION flow, plus the amount of SUCTION pressure built up in the suction vessel. Kinetic energy is converted back to pressure as the mixed media passes through the diverging taper and is discharged out the pump.


GL series jets have a motive pressure range of 60-120 psig and suction range of 6-30 inches.
GH series jets have a motive pressure range of 20-80 psig and a suction range of 6.5-30 inches.
Cast eductors can be made from 1/2 inch size to 4 inch size.
Fabricated eductors are 4 inches and up.
Non-Metallic are 1/2 to 3 inch size, these are PVC, Poly Pro, and Kynar.
The common metals are Cast Iron, Low Lead Bronze, Carbon Steel and 316L Stainless Steel.

www.flowfactor.com
866-360-9830

Friday, February 28, 2014

Skinner Four Way Valves

Parker Skinner Four Way valves for Actuation from Flow Factor


Skinner four-way solenoid valves are ideal for use in controlling double acting, pneumatic actuators or cylinders. Two-position, single or double solenoid models are designed for long, trouble-free life, and are available in 7700 Line, 7300 Line, and standard solenoid valves.
Four-way 7000, 7700 and 7300 Line valves have many of the same standard features found in the line’s three-way valves, including a unique seal, spool and cage design, integral pilot filtration and contamination tolerant design. They are available in brass or 303 stainless steel body materials. Skinner 7000 Series four-way valves are available in aluminum body material. These four-way valves have a maximum pressure differential of 150 PSI, with a Cv flow factor of 0.55 or 1.2 for 7700 and 7300 Line valves and 0.35, 1 or 1.4 for 7000 Series valves.

PARKER 4-Way Solenoid Valve 04F48S2106ACF4C01, 24 VAC, 1/4 NPT, single solenoid, 10-100 psi, Buna N 04F48S2106ACF4C01

PARKER 4-Way Solenoid Valve 04F48S2106A3F4C80, 24 VDC, 1/4 NPT, single solenoid, 10-100 psi, Buna N 04F48S2106A3F4C80

PARKER 4-Way Solenoid Valve 04F48S2106ACF4C05, 120 vac, 1/4 NPT, single solenoid, 0-150 psi, Buna N 04F48S2106ACF4C05

PARKER 4-Way Solenoid Valve 73417 Series, 120 vac, 1/4 NPT, single solenoid, 0-125 psi air, 0-100 psi  73417BN2PN00N0C111P3

PARKER 4-Way Solenoid Valve 73417 Series, 120 vac, 1/4 NPT, single solenoid, 0-150 psi air, 0-100 psi 73417BN2PN00N0C222P3

PARKER 4-Way Solenoid Valve 73417 Series, 24 dc, 1/4 NPT, single solenoid, 0-125 psi air, 0-100 psi 73417BN2PN00N0C111C2


PARKER 4-Way Solenoid Valve 73417 Series, 120 vac, 1/4 NPT, single EP solenoid, 0-125 psi air, 0-100 73417BN2PN00N0H111P3

Call flow Factor for all your 4 way Solenoid valve needs.
866-360-9830
www.flowfactor.com




Friday, January 31, 2014

Parker GP / General Purpose Solenoid Valves

Parker GP Solenoid Valves from FLOW FACTOR


General Purpose Solenoid Valves Normally Closed

Type 1 two-way solenoid valves can be used on either low or high pressure. The smaller valves are direct acting while the larger valves are pilot operated.
Applications:
These valves are for general application on non-corrosive fluids such as air, water below 180°F, light oils below 300 SUS, and low vacuum.  All seal off bubbletight.

Type 3 two-way solenoid valves have a brass body with a stainless steel seat insert and a teflon diaphragm.
Applications:
These valves are developed primarily for use on hot water and low pressure steam (to 10psi), but can be used on air and other non-corrosive fluids.  They can be used with fluid temperatures ranging from  -20° F to 240° F.

Type 4 two-way solenoid valves have a brass body with a stainless steel seat insert and an ethylene propylene (EPT) diaphragm and seals. 
Applications:
These valves are recommended for steam service up to 50 psig saturated steam.


These valves uses the G23 coils.

PARKER GP23 coil, 24 VAC for Parker GP valves  part number 77300

PARKER GP23 coil, 120 VAC for Parker GP valves  part number 77310

PARKER GP23 coil, 240 VAC for Parker GP valves  part number 77320

PARKER GP23 coil, 480 VAC for Parker GP valves   part number 77340

PARKER GP23 coil, 120/240 VAC for Parker GP valves  part number 77360

PARKER GP23 coil, 12 vdc for Parker GP valves  part number 75520

PARKER GP23 coil, 24 vdc for Parker GP valves  part number 75530


GP 200  is part number 70221
GP 207  is part number 70222
GP 257  is part number 70223
GP 300  is part number 70393
GP 307  is part number 70393
GP 357  is part number 70223
GP 400  is part number 70562
GP 407  is part number 70563
GP 457  is part number 70564
GP 600  is part number 70712
GP 607  is part number 70713
GP 657  is part number 70714
GP 10A  is part number 70810
GP 1007 is part number 70808
GP 1057 is part number 70777
(The GP valve numbers are linked at the top of the page under their descriptions.)


www.flowfactor.com
866-360-9830

Wednesday, January 1, 2014

Penberthy Type SF Site Flows - Dimensions

Pentair - Penberthy Dimensions for Series SF Site Flows  - Flow Factor


SERIES SF SIGHT FLOW INDICATORS – MODELS SF, SFD, SFF, SFR, SFG, SFB


Penberthy Model SF is a plain site flow, no indication except visual
Penberthy Model SFF is a Flapper style site flow with a Flapper that moves within the Site Flow
Penberthy Model SFR is a Rotator style site flow with a whirly/rotating pinwheel within the site flow.
Penberthy Model SFD is a drip tube style Site Flow
Penberthy Model SFG is a Gaseous style sight flow.













Please contact us for ordering, quoting or more information regarding Pentair / Penberthy Site Flows

216-765-4231
info@flowfactor.com