Littelfuse 777 Accupower Power Monitor

Littelfuse 3-Phase Current & Voltage Monitor 777-Accupower

Request a Quote HERE!

The Littelfuse 777-AccuPower is a fully-programmable 3-phase motor and pump protection relay. It allows motor hp rating, full load amps, efficiency and power factor to be entered and will accurately calculate motor output power. This is most useful with mag-drive pumps or process applications where the process power is desired over the utility power. Voltage, current and power measurements can be displayed as well as fault information and setpoints. The built-in display simplifies troubleshooting and allows the user to easily and precisely configure setpoints. The Littelfuse 777-AccuPower can be used with the optional COM 4-20 output module to give an analog signal proportional to output shaft power, the RS485MS-2W (for limited Modbus capabilities, and for use with the RM1000/RM2000) remote displays listed in the 777 accessories section.

Features & Benefits:

Motor output power measurement 
Allows use of process power over utility power 
 
3 programmable restart delay timers 
Program separate restart delay time for rapid cycle protection, motor cool down, and dry-well recovery 
 
Built-in Display 
Visual indication for programming, viewing real-time voltage or current, and last fault code 
 
Remote display compatibility 
Increases safety through remote display of run-hour meter, last four fault codes, without the need to open the cabinet. Aids with arc flash safety regulations
 
Network communications capability
Limited Modbus capabilities using RS485MS-2W communication module

 

Littelfuse 777-Accupower 3-Phase motor and pump monitor

 

 

 

 

 

 

 

 

 

Specifications:

Input Characteristics 

Line Voltage 200- 4 80VAC

Frequency50/60Hz 

Motor Full Load Amp Range 2-800A (external CTs required over 90A) 

Functional Characteristics 

TC- Overcurrent Trip Class 5, 10, 15, 20, 30(J prefix enables jam protection feature)

 Output Characteristics 

Output Contact Rating (SPDT - Form C) 

Pilot duty 4 80VA @ 24 0VAC

General Purpose10A @ 240VAC

General Characteristics 

Ambient Temperature Range 

Operating-40° to 70°C (-40° to 158°F)Storage -40° to 80°C (-40° to 176°F) 

Accuracy  --  Measured Horsepower/ Kilowatt 

Typical    ± 3 %* * 

Voltage    ±1% 

Current   ±3%

(<100 amps direct)

GF Current   ±15% Timing   5% ±1 second 

Repeatability 

Voltage  ±0.5% of nominal voltage 

Current  ±1% (<100 amps direct) 

Maximum Input Power   10 W 

Pollution Degree    3 

Class of Protection   IP20, NEMA 1 (finger safe)

Relative Humidity    10-95%, non-condensing per IEC 68-2-3 

Terminal Torque    7 in.-lbs

Standards Passed
 
Electrostatic Discharge:  (ESD):   IEC 61000-4-2, Level 3, 6kV contact, 8kV air 
Radio Frequency Immunity (RFI), Conducted:    IEC 61000-4-6, Level 3 10V/m 
Radio Frequency Immunity (RFI), Radiated:    IEC 61000-4-3, Level 310V/m 
Fast Transient Burst:   IEC 61000-4-4, Level 3, 3.5 kV input power 
Short Circuit Rating:     100k A 
 
Surge
 
IEC:   61000-4-5 Level 3, 2kV line-to-line; Level 4, 4kV line-to-ground 
ANSI/IEEE:   C62.41 Surge and Ring Wave Compliance to a level of 6kV line-to-line
Hi-Potential Test:   Meets UL508 (2 x rated V + 1000V for 1 min.) 
Vibration:   IEC 68-2-6, 10-55Hz, 1mm peak-to-peak, 2 hrs, 3 axis 
Shock:   IEC 68-2-27, 30g, 3 axis, 11ms duration, half-sine pulse 
 
Safety Marks 
 
UL:     UL508, UL1053
CE:     IEC 60947-1, IEC 60947-5-1 
CSA:    C22.2
Max. Conductor Size through 777:   0.65” with insulation 
Dimensions :   H 77.47 mm (3.05”); W 97.79 mm (3.85”); D 128.27 mm (5.05”)  
Weight:    1.3 lbs. (20.8 oz., 589.67 g) 
Mounting Method:   Surface mount (4 - #8 screws) or DIN rail mount 
 
**On a well balanced system within recommended current range.
 
 
Littelfuse Model Number
777-AccuPower
 
Accessories:

Littelfuse RS485MS-2W Communication Module
(for limited Modbus capabilities)Required to enable the Modbus communications function on Model 77X-type products.
  
Littelfuse COM 4-20 Output Communication Module
This module allows communication to a PLC with an analog input and no Modbus input.
 
Littelfuse RM1000 Remote Monitor
The RM1000/777 motor management system combines unsurpassed electronic motor protection and critical, user-friendly, motor monitoring for up to 16 devices.
 
Littelfuse RM2000 Remote Monitor
The RM2000/777 motor management system combines unsurpassed electronic motor protection and critical, user-friendly, motor monitoring with event storage and real-time clock for date and time stamp.
 
Request a Quote HERE!
 
Flow Factor
216-765-4231
 
Littelfuse 777-Accupower...Littelfuse 777-Accupower

Monday, October 26, 2020

Littelfuse PC-102 Series Pump Controllers

 Littelfuse PC-102 Series Pump Controllers from Flow Factor

For a Quote, Click HERE!

Littelfuse PC-102CICI-DL:

Dual seal-leak detector uses inputs to sense seal failures and energize the output relay. Input logic direct or inverted is DIP switch selectable.

Littelfuse PC-102CICI-LT:

Seal-leak and over-temperature detector uses one input to sense seal failures and the temperature input to detect motor overheating. Configurable to suit various probes. Seal input logic direct or inverted, plus over-temperature trip reset automatic or manual, is DIP switch selectable. 

Littelfuse PC-102 Pump Protection Controller










Littelfuse PC-102 Description

The LIttelfuse PC-102 series is a dual-channel switch that provides dual protection against seal failures and over-temperature in submersible pumping applications.

The relays have two form-C isolated output relays and two LEDs, which illuminate when each associated output relay is energized.

The sensitivity adjustment (4.7k-100kOhms) allows you to define the input impedance at which the output relays will change state. The sensitivity for the over-temperature detector can be set to 4k Ohms with use of the DIP switches.

Littelfuse PC-102 Specifications

Input Characteristics 

Frequency 50/60Hz 

Functional Characteristics: 

Probe Sense Voltage 5vdc pulsed 

Sensitivity 4.7k-100kΩ Sensitivity (for temp) Selectable 4kΩ with DIP switches 

Input Logic Direct or inverted 

Debounce Time Delay 0.5 or 2 seconds 

Output Characteristics:

Relay Output Rating (2 Form C isolated) 

Pilot Duty 180VA @ 120VAC, C150,  General Purpose 5A @ 240VAC 

General Characteristics: 

Temperature Range -20° to 55°C (-4° to 131°F) 

Maximum Input Power 2 W 

Depluggable Connector Phoenix Contact-Series MSTB plugs 

Output Relay Status Indicators LEDs 

Terminal Torque 4.5 in.-lbs. 

Wire range 12-20 AWG 

Standards Passed:

Electrostatic Discharge (ESD) IEC 61000-4-2, Level 3, 6kV contact, 8kV air. 

Radio Frequency Immunity (RFI) IEC 61000-4-3, Level 3, 10V/m 

Fast Transients IEC 61000-4-4, Level 3, 4kV input power 2kV inputs/outputs 

Safety Marks: 

UL UL508 (File #E68520) 

Dimensions H 88.9 mm (3.5”); W 52.93 mm (2.08”); D 59.69 mm (2.35”) 

Weight 0.9 lb. (14.4 oz., 408.23 g) 

Mounting Method 35mm DIN rail or Surface Mount (#6 or #8 screws)

For a Quote, Click HERE!

Flow Factor

216-765-4231

www.flowfactor.com

Littelfuse...PC-102...Littelfuse...PC-102...Littelfuse...PC-102...Littelfuse...PC-102

Saturday, October 24, 2020

5 Channel Pump Controller from Littelfuse - PC-105

PC-105 Series - 5-Channel Pump Controller

from Littelfuse and Flow Factor

For a Quote, Click HERE!

The Littelfuse PC-105 is a 5-channel pump controller designed to handle multiple pump applications. Alternatively, it can operate as a 5-channel switch. The Little Fuse PC-105’s control functions support all of the popular industry standard multi-pump pump-up and pump-down configurations. It can indicate low, high and out-of-sequence alarms and use alternating and non-alternating pump control. The non-alternating pump can be used as a jockey pump or emergency pump. Using the built-in DIP switches, individual pumps can be disabled when taken out of service for repair or maintenance.

Littelfuse PC-105 Five Channel Pump Control









Features:

Compact Design

Low, High and Out of Sequence alarms

Variable time delay/lag pump delay from 2-255 seconds

DuPlex SPS (seperate pump stop) pump control

DuPlex, TriPlex or QuadraPlex pump control

Pump-up or pump-down functions

External Silence, reset and alternation configuration

Five Channel Relay Configuration

DIN rail or surface mountable

SPECS:

120 VAC supply power

50/60 hz frequency

Probe Sense Voltage is 5vdc continuous

Relay Output Rating is 7 am[ps @240 VAC

Max Input Power is 4 watts

12-20 AWG wire size range

Pump In-Rush delay is 2 seconds

Electrostatic discharge  (ESD) is IEC 61000-4-2, Level 3, 6kV contact, 8kV air

Radio Frequency Immunity (RFI) is Level 3, 10V/m

Fast Transients is Level 3, 4kV input power

UL listed UL508

Dimensions: 3.7 x 5.0 x 2.4 inches and 1.2 Pounds

Littelfuse PC-105 Pump Control Wiring












For a Quote, Click HERE!

Flow Factor

216-765-4231

www.flowfactor.com

Littelfuse...PC-105...Littelfuse...PC-105...Littelfuse...PC-105...Littelfuse...PC-105

Wednesday, September 30, 2020

Pump Control from Littelfuse - PC-XXX-LLC Series

 Pump Control from Littelfuse in Small Package - Octal Socket

The Littelfuse PC-xxx-LLC-CZ and PC-xxx-LLC-GM series are liquid level control relays used to control conductive liquid pumping operations in a pump-up or pump-down application. The units come in two different voltage ranges (see specs below). The units have an adjustable sensitivity knob (4.7 k to 100 k ohms) that is set according to the resistance level at which you want the probes (sold separately) to sense the conductive liquid. The units have a built-in debounce time delay that prevents the relay from energizing if the probe resistance momentarily goes above or below the sensitivity set point (due to liquid splashing in the tank). The Little Fuse units operate their internal relay based on inputs from a high and low probe and a common reference (when a conductive tank is used) or common probe (when a non-conductive tank is used). 

Click HERE for a quote

Littelfuse Pump Protection Relay










Littelfuse - PC-XXX-LLC-CZ 

Compatible with Crouzet PNR & PNRU Series Liquid Level

Littelfuse - PC-XXX-LLC-GM

Compatible with Gems 16M Series Liquid Level

Specifications:

Supply Voltage:

PC-100-LLC_CZ ... 95-120VAC

PC-100-LLC_GM ... 95-120VAC

PC-200-LLC_CZ ... 190-240VAC

PC-200-LLC_GM ... 190-240VAC

Frequency 50/60 Hz

Probe Sense Voltage is 5VDC pulsed

Debounce Time Delay is 2 seconds

Probe sensitivity is 4.7k to 100k Adjustable

Output contact rating is 10A @ 240VAC

Approvals are UL and CE

Mounting is via Octal Socket; DIN rail or surface

Octal socket part number is OT08PC